CVE Intelligence
Skip to main content
HIGH

CVE-2019-25719

CVE-2019-25719 — Dräger Infinity M540 VG4.1.1 Spoofing and DoS via Network Message Handling

Dräger Infinity Acute Care System and Standalone Infinity M540 patient monitors running software versions VG4.1.1, VG4.0.3, and lower contain network message handling vulnerabilities that allow network-adjacent attackers to spoof or tamper with data and cause denial-of-service conditions. Attackers with access to an enabled Infinity network port or physical proximity to a wireless access point can modify device settings such as alarm states or alarm limits, and overwhelm the system with incoming data causing the device to reboot and lose network functionality.

Published Updated Sources: cvelistV5, VulnCheck

Triage

Is it exploited, how likely is exploitation, what does it touch, and how severe do the scoring sources call it.

Exploitation

Unreported

no source claims exploitation

EPSS

0%

chance of exploitation in 30 days

Affects

dr ger

2 products listed

CVSS base

8.6

HIGH

CISA SSVC assessment

Three decision points CISA publishes for the CVEs it assesses · SSVC 2.0.3. A stakeholder decision, not a severity score.

CISA

Exploitation

None

none · proof-of-concept · active

Automatable

Yes

can an attacker script all four kill-chain steps

Technical impact

Partial

partial · total control of the vulnerable component

Affected scope

The catalog records vendors and products as separate lists, not pairs, so which product belongs to which vendor is not something this page can say.

Vendors (1)

Products (2)

infinity acute care systemstandalone infinity m540 patient monitor

Every base score collected

Sources score independently and disagree; each row says who scored it and under which version.

ScoreVersionSeverityExpl.ImpactSource
8.6CVSS 3.1HIGHcvelistV5

Weakness & attack patterns

  • CWE-924

References

2 on the record

Elsewhere on this site

  • dr gerevery CVE for this vendor
  • CWE-924other pages naming this weakness

Not in any source we poll

Listed rather than left blank: an empty field and an unmeasured one look identical on screen, and only one is a reason to look elsewhere.

  • No confirmed IOCs, IP addresses, domains, file hashes, or malware artifacts supplied.
  • No organization-specific asset inventory, compensating-control status, or patch deployment evidence supplied.
  • No exploit packet captures, log samples, or incident case IDs supplied.